Cable Construction
Stranded copper conductor plain PVC conductor insulation according to UL-Std. 1581 class 43 and CSA-C22.2 No.
210 UL VW-1 and CSA
FT1, heat and damp resistant properties
Technical Data
PVC insulated jumper wire to UL AWM Style 1015 and CSA-AWM as per UL Style 1015
Temperature Range
Flexible -5°C to +105°C (+ 23°F to + 221°F)
Fixed installation -30°C to +105°C ( 22°F to + 221 °F)
Temperature at Conductor
Max. UL and CSA: + 105°C/+ 221 °F
Nominal Voltage
600 V
Properties
PVC self-extinguishing and flame retardant, test method to UL VW-1/CSA FT1. The materials used in manufacture are RoHS compliant.
Test Voltage (spark Test)
AWG 24 = 4 Kv
AWG 22 and 20 = 5 kV
AWG 18 to 10 = 6 kV
?AWG 8 = 7.5 kV
UL-Type AWM + 105°C/+ 221°F
Bending Radius
Approx. 5 x cable ϕ
AWM - Appliance Wiring Material. Intended for Internal wiring of appliances UL - Underwriters Laboratories Inc. (USA) CSA -Canadian Standards Association (Canada) CE. The product is conformed with the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC.
Dimensions
Cross Section Area Sq. mm | AWG No. | Nom Insulation Thickness mm | Approx. Cable Diameter mm |
0.4 |
22 |
0.78 |
2.6 |
0.7 |
20 |
0.78 |
2.8 |
0.9 |
18 |
0.78 |
2.9 |
1.3 |
16 |
0.78 |
3.2 |
2.2 |
14 |
0.78 |
3.6 |
3.4 |
12 |
0.78 |
4.2 |
5.2 |
10 |
0.78 |
4.7 |
8.8 |
8 |
1.143 |
6.4 |
14.7 |
6 |
1.524 |
8.5 |
22.8 |
4 |
1.524 |
9.6 |
33.1 |
2 |
1.524 |
10.9 |
46.1 |
1 |
2.04 |
13.3 |
67.3 |
2/0 |
2.04 |
15.3 |
86.9 |
3/0 |
2.04 |
17.1 |
110.1 |
4/0 |
2.04 |
18.5 |
135.8 |
250 MCM |
2.42 |
21.00 |
177.0 |
350 MCM |
2.42 |
22.9 |
227.7 |
450 MCM |
2.42 |
25.6 |